Refine your search

1 vulnerability found for CODESYS PROFINET by CODESYS

CVE-2026-35226 (GCVE-0-2026-35226)
Vulnerability from cvelistv5
Published
2026-07-29 07:05
Modified
2026-07-29 14:27
CWE
Summary
An out‑of‑bounds write vulnerability in the CODESYS PROFINET Controller allows an unauthenticated attacker on the same network segment to send malformed PROFINET communication data that triggers an exception in the affected PLC application. The exception is handled by the CODESYS Control runtime system and results in a controlled stop of the PLC application.
Impacted products
Vendor Product Version
CODESYS CODESYS PROFINET Version: 4.4.0.0   
Create a notification for this product.
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2026-35226",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2026-07-29T14:27:26.242820Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2026-07-29T14:27:45.179Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "CODESYS PROFINET",
          "vendor": "CODESYS",
          "versions": [
            {
              "lessThan": "4.8.0.0",
              "status": "affected",
              "version": "4.4.0.0",
              "versionType": "semver"
            }
          ]
        }
      ],
      "cpeApplicability": [
        {
          "nodes": [
            {
              "cpeMatch": [
                {
                  "criteria": "cpe:2.3:a:codesys:codesys_profinet:*:*:*:*:*:*:*:*",
                  "versionEndExcluding": "4.8.0.0",
                  "versionStartIncluding": "4.4.0.0",
                  "vulnerable": true
                }
              ],
              "negate": false,
              "operator": "OR"
            }
          ],
          "operator": "OR"
        }
      ],
      "credits": [
        {
          "lang": "en",
          "type": "finder",
          "value": "ABB"
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cp\u003eAn out\u2011of\u2011bounds write vulnerability in the CODESYS PROFINET Controller allows an unauthenticated attacker on the same network segment to send malformed PROFINET communication data that triggers an exception in the affected PLC application. The exception is handled by the CODESYS Control runtime system and results in a controlled stop of the PLC application.\u003c/p\u003e"
            }
          ],
          "value": "An out\u2011of\u2011bounds write vulnerability in the CODESYS PROFINET Controller allows an unauthenticated attacker on the same network segment to send malformed PROFINET communication data that triggers an exception in the affected PLC application. The exception is handled by the CODESYS Control runtime system and results in a controlled stop of the PLC application."
        }
      ],
      "metrics": [
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "LOW",
            "attackRequirements": "NONE",
            "attackVector": "ADJACENT",
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "privilegesRequired": "NONE",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "NONE",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "NONE",
            "vulnIntegrityImpact": "NONE",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        },
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "ADJACENT_NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "NONE",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-787",
              "description": "CWE-787 Out-of-bounds Write",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2026-07-29T07:05:57.508Z",
        "orgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
        "shortName": "CERTVDE"
      },
      "references": [
        {
          "url": "https://www.certvde.com/en/advisories/VDE-2026-041/"
        }
      ],
      "source": {
        "advisory": "VDE-2026-041",
        "defect": [
          "CERT@VDE#642012"
        ],
        "discovery": "UNKNOWN"
      },
      "title": "Out-of-bounds Write in CODESYS PROFINET Controller",
      "x_generator": {
        "engine": "Vulnogram 0.4.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "270ccfa6-a436-4e77-922e-914ec3a9685c",
    "assignerShortName": "CERTVDE",
    "cveId": "CVE-2026-35226",
    "datePublished": "2026-07-29T07:05:57.508Z",
    "dateReserved": "2026-04-01T19:54:21.499Z",
    "dateUpdated": "2026-07-29T14:27:45.179Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.2"
}