Refine your search

1 vulnerability found for SIMATIC IoT2050 Advanced by Siemens

CVE-2026-58115 (GCVE-0-2026-58115)
Vulnerability from cvelistv5
Published
2026-08-11 12:20
Modified
2026-08-12 19:19
CWE
  • CWE-306 - Missing Authentication for Critical Function
Summary
A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions < V4.3.4.1 running Industrial OS with Node-RED installed). Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server. This could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges.
Impacted products
Vendor Product Version
Siemens SIMATIC IoT2050 Advanced Version: 0   < V4.3.4.1
Create a notification for this product.
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2026-58115",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2026-08-12T17:59:33.476267Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2026-08-12T19:19:54.001Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unknown",
          "product": "SIMATIC IoT2050 Advanced",
          "vendor": "Siemens",
          "versions": [
            {
              "lessThan": "V4.3.4.1",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "value": "A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions \u003c V4.3.4.1 running Industrial OS with Node-RED installed). Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server.\r\nThis could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "baseScore": 10,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H",
            "version": "3.1"
          }
        },
        {
          "cvssV4_0": {
            "baseScore": 10,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H",
            "version": "4.0"
          }
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-306",
              "description": "CWE-306: Missing Authentication for Critical Function",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2026-08-11T12:20:24.045Z",
        "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
        "shortName": "siemens"
      },
      "references": [
        {
          "url": "https://cert-portal.siemens.com/productcert/html/ssa-834709.html"
        }
      ]
    }
  },
  "cveMetadata": {
    "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77",
    "assignerShortName": "siemens",
    "cveId": "CVE-2026-58115",
    "datePublished": "2026-08-11T12:20:24.045Z",
    "dateReserved": "2026-06-29T12:59:54.795Z",
    "dateUpdated": "2026-08-12T19:19:54.001Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.2"
}